30
5.2
Configurable Input Types
Input devices and modules may be configured as one of many possible input types. Table 8
identifies the device types assignable to each input type. For device type descriptions see
sections 5.2.1 to 5.2.12.
5.2.1
Alarm Input (Non-Verified)
An un-bypassed, non-verified alarm input entering into alarm activates the common alarm
sequence.
Common Alarm Sequence
•
Updates un-bypassed relay, signal, and strobe outputs based upon their configuration.
•
Activates Alarm zone status indicators associated with the input.
Table 8 Configurable Input Types
Input Type
As listed in
Configurator
Description
located in
Section number
Device Types
Detectors
Dual Mini Modules
Zone Module
Mini Monitor Module
Monitor Module
Alarm Input
Alarm Input
5.2.1
X
X
Latched Supervisory
Latched Supv
5.2.2
X
X
Building/Property Safety
Input
Building
5.2.3
X
X
Non-Latching
Supervisory
Non-Latch Supv
5.2.2
X
X
Priority Alarm
Priority Alm
5.2.4
X
X
Trouble Input
Trouble Input
5.2.5
X
X
Waterflow Alarm Input
Waterflow
5.2.6
X
System Reset
Sys Reset
5.2.7
X
Fire Drill
Fire Drill
5.2.7
X
Acknowledge
Ack
5.2.7
X
Total Evacuation
Total Evac
5.2.7
X
Auxiliary Disconnect
Aux Disc
5.2.7
X
Buzzer Silence
Buzz Sil
5.2.7
X
Signal Silence
Signal Silence
5.2.7
X
Acknowledge General
Alarm
Ack GA
5.2.7
X
Audible Walktest
Audible Walktest
5.2.8
X
Silent Test
Silent Test
5.2.9
X
Manual Day/Night
Manual Day/Night
X
Auto Day/Night
Auto Day/Night
X
Auxiliary Reset
Auxiliary Reset
5.2.7
X
Verified Alarm
Verified Alm
5.2.12
X