12.0 Appendix E - Battery Calculations
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated continuous power without provision of any
disconnect devices. Use #12 AWG wire with 600 volt insulation and proper over-current circuit protection that complies with the local
codes. For specifications see Appendix D - Specifications And Features on page 92.
Power Requirements (All currents are in amperes)
Model Number
Description
Qty
Standby
Total
Standby
Alarm
Total
Alarm
FX-3500
FX-3500 FACP with Dialer
X
0.390
=
0.630
=
ALC-636
636 Point Dual Loop Adder
X
0.120
=
0.200
=
RAM-3500-LCD
Remote Annunciator with 4-
line LCD Display
X
0.070
=
0.100
=
RAX-LCD-LITE
Remote Annunciator with 4-
line LCD Display
X
0.065
=
0.080
=
PR-300
Polarity Reversal and City
Tie Module
X
0.050
=
0.300
=
SRM-312W/312R
Smart Relay Module
X
0.030
=
=
RAM-1016TZDS
16 Point Annunciator
Chassis
X
0.050
=
0.150
=
RAM-1032TZDS
32 Point Remote
Annunciator
X
0.050
=
0.300
=
RAX-1048TZDS
48 Point adder annunciator
display
X
0.022
=
1 zone active: 0.026
2 zone active: 0.030
3 zone active: 0.035
4 zone active: 0.039
48 zone active: 0.262
=
IPS-2424DS
Programmable Input
Switches Module with 24
switches
X
0.005
0.022
=
IPS-4848DS
Programmable Input
Switches Module with 48
switches
X
0.010
0.022
=
RTI-1
Remote Trouble Indicator,
Buzzer and LED
X
0.035
=
0.035
=
MIX-1251AP(A)
Advanced Protocol Ion
Smoke Detector (ULC)
X
0.0003
=
0.0050
=
MIX-2251AP(A)
Advanced Protocol Photo
Smoke Detector (ULC)
X
0.00036
=
0.0050
=
MIX-2251TAP(A)
Advanced Protocol Photo
Heat Detector (ULC)
X
0.00036
=
0.0050
=
MIX-2251TMAP(A)
Advanced Protocol
Acclimate Detector (ULC)
X
0.00036
=
0.0050
=
MIX-5251AP(A)
Advanced Protocol Heat
Detector (ULC)
X
0.0003
=
0.0050
=
MIX-5251HAP(A)
Advanced Protocol High
Temperature Heat Detector
(ULC)
X
0.0003
=
0.0065
=
MIX-5251RAP(A)
Advanced Protocol Rate of
Rise Heat Detector (ULC)
X
0.0003
=
0.0065
=
MIX-M500MAP(A)
Advanced Protocol Monitor
Module (ULC)
X
0.0004
=
0.0052
=