22
4.6
Installing the ALC-636 Dual Loop Adder
Mount the ALC-636 Dual Loop Adder as shown in Figure 6.
The panel can provide up to 350mA of alarm current to the devices on the loop. For device
currents see Appendix E - Battery Calculations on page 94.
Figure 7
Installing the ALC-636 Dual Loop Adder
Table 4 PR-300 Polarity Reversal and City Tie Module Connectors and Jumpers
Item
Setting
P1
Connect cable to P8 on the Main Board of the FX-3500
JW4
Not used. Keep jumper intact.
Notes:
If using a PR-300 remember to remove JW7 on the main board. For the location
of JW7 on the main board see Figure 3.
Table 5 ALC-636 Dual Loop Adder Connectors and Jumpers
Item
Setting
P1
Connect cable to
P10
on the Main Board of the FX-3500.
i
Mounted on hex spacer
with four screws provided
ALC-636
A L
OOP1
B
+
-
+
-