33
5.2.7
System Status Correlations
The following System Status processes can be correlated to configured (mini) monitor
modules:
•
System Reset
•
Fire Drill
•
Acknowledge
•
Total Evacuation
•
Buzzer Silence
•
Signal Silence
•
Acknowledge General Alarm
•
Auxiliary Disconnect
5.2.8
Audible Walktest
Configures (mini) monitor modules as audible when conducting a walktest. For more
information on performing a walktest see 5.11.6 Walk Test.
5.2.9
Silent Test
Configures (mini) monitor modules as silent when conducting a walktest. For more information
on performing a walktest see 5.11.6 Walk Test.
5.2.10
Manual Day/Night
Configures (mini) monitor modules for manual day/night alarm thresholds. For more
information on alarm thresholds see 5.1.3 Alarm Conditions.
5.2.11
Auto Day/Night
Configures (mini) monitor modules for auto day/night alarm thresholds. For more information
on alarm thresholds see 5.1.3 Alarm Conditions.
5.2.12
Verified Alarm Input
Un-bypassed verified alarm inputs entering into alarm are verified over a period of time to
determine if the alarm condition is valid.
Addressable
/
Analog Device Verification Process
If the system is not already in alarm:
1. A device entering into alarm initiates a 30 second delay timer.
2. When the 30 second delay times out the device is monitored for the next 60 seconds.
3. If the same device enters into alarm again during this time the alarm is confirmed. The
following will also confirm the alarm:
•
Any additional Alarm Input activating aborts the verification process and confirms
the alarm.
•
Any trouble detected on the circuit being verified aborts the verification process
and confirms the alarm.
Attention: Devices correlated with any of the above System Statuses need to be
contained within a secured enclosure accessibly only to those with the
proper authority.
!