Technical Manual – IP Router SCN-IP100.03
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
17
17
3.3 Mixed operation
IP Secure
Secured devices can only communicate with devices that are also secured. Mixtures of e.g. secured
KNX IP Secure couplers with unsecured KNX IP Secure devices or normal KNX IP devices will not work.
Data Secure
With Data Secure, devices that support Data Secure can also communicate with devices that do not
support Data Secure. A mixed operation in one project is therefore possible.
However, if all data of a group address are to be transmitted in encrypted form, all devices whose
objects are connected to this group address must support Data Secure.
3.4 Commissioning
ETS requires the following procedure to put Secure devices into operation:
1.
Load product data
When loading the product database, you will normally be asked directly to enter the FDSK of
the device:
Figure 8: Enter FDSK
You can enter the FDSK manually or read the QR code from a camera. If you do not want to
read the FDSK directly or if you do not have it at hand, you can do this later by confirming
this dialogue with "Later".