Green
Red
LED 1
Bus State - LAN
Off: LAN Error
On: LAN OK
On: Manual Mode active
LED 2
Bus State - KNX
Off: KNX Bus: Error or not connected
On: KNX Bus OK
LED 3
Traffic - LAN
Flashing: Bus load at LAN-side
Off: No Bus load at LAN-side
Speed up to 10 Mbit/s
Flashing: Transmission error at LAN
side
LED 4
Traffic - KNX
Flashing: Bus load at KNX side
Off: No Bus load at KNX side
Flashing: Transmission error at KNX
side
LED 5
Forwarding of
group telegrams
Forwarding of group telegrams
- Off: LAN and KNX different
- Filter table activ
Lock
Green and Red: forwarding all
LED 6
Forwarding of
physical addresses
Forwarding of physical addresses
- Off: LAN and KNX different
- Filter table activ
Yellow: Lock
Green and Yellow: forwarding all
Table 1: Overview LEDs
2.5 Commissioning without Data Secure
The following procedure is recommended for commissioning the SCN-IP100.03:
1.
Insert the application „SCN-IP000.03 – KNX IP Router“
2.
Configuration of the IP-Router:
3.
Transfer of the physical address and the application of the IP Router. For this, the
programming button must be
pressed shortly
. The programming LED
lights steadily red
.
4.
After successful transfer of the physical address and the application, the red LED turns off
again.
5.
Insert the application „SCN-IP000.03 – KNX IP Router with email function“
6.
Configuration of the E-Mail Client:
7.
Transfer of the physical address and the application of the E-Mail Client. For this, the
programming button has to be
pressed long
. The programming
LED flashes red
.
8.
After successful transfer of the physical address and the application, the red LED turns off
again.
9.
Accessing the Web client to configure the e-mail addresses by opening an Internet browser
and call the address: http:\\IP address: port, for example: http: \\192.168.1.178:8080 for the
IP address 192.168 .1.178 and the http port 8080
Important:
If the IP address of the IP Router gets changed subsequently, the device must perform a
reboot. This restart is not performed automatically by the application programming in the ETS4/5.
Here, a manual restart will be required, which either by right-clicking on the device and selecting
"Reset device" is executed or a short removing of the bus connector.