MAC Address
Specified by the unit.
Multicast Address
The multicast address is specified by the backbone and can be changed in the project in the tab
"Topology Backbone".
Commissioning Password
Set the start-up password (optional), see also “3 Safety – IP Secure/Data Secure”.
Authentication Code
Specify the authentication code (optional), see also “3 Safety – IP Secure/Data Secure”.
4.2 Settings IP Interface without Secure
4.2.1 General
The following parameters can be set in the "General" submenu:
Figure 13: General Settings (without Secure)
The following table shows the setting options for this submenu:
ETS-Text
Dynamic Range
[Default value]
Comment
Host name (30 signs)
any
[MDT KNX IP Router]
Any name can be chosen here, but it
should be as meaningful as possible.
Enable slow
connections
enable
disable
Adjust the timeout for tunneling
connections. By default, slow connections
are not supported and a short timeout is
used for the UDP connection. This can be
increased by supporting slow connections
which may be necessary especially for
tunnel connections over the internet.
Fallback time for
manual operation
10 min
1 hour
4 hours
8 hours
Setting of the automatic release time
from manual mode to automatic mode
Manual function
disabled
pass all telegrams
pass physical telegrams
pass group telegrams
Defines the behavior after manual
changeover
Table 3: General Settings (without Secure)