Technical Manual – IP Router SCN-IP100.03
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
41
41
Length 1 Byte
Data point type
Dynamic range
1 Byte value
0-255
1 Byte Percent value
0-100%
1 Byte HVAC Status
0x01 -> Comfort
0x02 -> Standby
0x03 -> Night
0x04 -> Frost-/Heat protection
1 Byte HVAC Mode
The HVAC mode is evaluated bit by bit
and displayed:
Bit 0 -> 1 = Comfort
Bit 1 -> 1 = Standby
Bit 2 -> 1 = Night
Bit 3 -> 1 = Frost-/Heat protection
Bit 5 -> 0 = Cooling/ 1= Heating
Bit 7 -> 1 = Frost alarm
Table 11: Status elements – 1 Byte
Length 2 Byte
Data point type
Dynamic range
2 Byte unsigned value
0 – 65535
2 Byte signed value
-32768 – 32767
2 Byte floating value
-670760 – 670760
Table 12: Status elements – 2 Byte
Length 4 Byte
Data point type
Dynamic range
4 Byte unsigned value
0 – 4 294 967 295
4 Byte signed value
-2 147 483 648 – 2 147 483 647
4 Byte floating value
Floating point according to IEEE 754
Table 13: Status elements – 4 Byte
Length 14 Byte String
Data point type
Dynamic range
14 Byte String (ISO 8859-1)
Any string with max. 14 characters
Table 14: Status elements – 14 Byte
The following table shows the available communication objects:
Number
Name
Length
Usage
21
Status element 1
1 Bit
1 Byte
2 Byte
4 Byte
14 Byte
Setting the value of the status element
+1
next status element
Table 15: Communication objects – Status elements