5.2.3 Text Alarms
The figure below shows the available settings:
Figure 32: Settings – Text Alarm
The following table shows the settings available for an activated text alarm:
ETS-Text
Dynamic range
[Default value]
Comment
Waiting time until collected
14 byte telegrams are sent
out together
1 … 120 s
[10 s]
Setting the time window in
which text messages are
combined into one email.
Send email to destination
address 1
yes
no
Setting whether to send to
recipients 1
Send email to destination
address 2
yes
no
Setting whether to send to
recipients 2
Send email to destination
address 3
yes
no
Setting whether to send to
recipients 3
Table 18: Settings – Text Alarm
A text alarm is triggered as soon as a value is written to the corresponding communication object.
To send longer texts than 14 characters: After sending a value to the corresponding communication
object, the IP Router will wait the set waiting time.
If, within the set waiting time, another string has been sent to the communication object, all
collected strings are sent one after another in the email.
The table below shows the available communication objects:
Number
Name
Length
Usage
8
Text alarm 1
1 Bit
Setting the value for the text alarm
+1
next Text alarm
Table 19: Communication objects – Text Alarm