Appendix A – ME-ARC Compatibility Matrix
©
2014 Magnum Energy, Inc
.
Page 128
Button
Features/Settings
Model/
Level
Required
Default
Main
Menu
Menu
Heading/Item
Selections/
Adjustments Range
SETUP
03
Char-
ger
Setup
03C Battery Type
Gel, Flooded, AGM1, AGM2
≥
Level 1
Flooded
Absorb (12.0-16.0)*
≥
Level 3 [2]
14.4*
Float (12.0-16.0)*
13.2*
EQ (12.0-16.0)*
15.6*
EQ Done (0.1-25.5)
4.0 Hrs
CC/
CV
Max Charge =
OFF, 20-990ADC
≥
Level 4
200ADC
CV Charge =
12.0-16.0* VDC
13.8*V
CV Chg Done = Time,
Amps, Hold CV Chg VDC
Time
Time = 0.1-25.5
2 Hrs
Max CC/CV Time =
OFF, 0.1-25.5 Hrs
12 Hrs
Recharge Volts =
12.0-16.0* VDC
12.0*V
Amps = 0-250 ADC
20 ADC
Max CC/CV Time =
OFF, 0.1-25.5 Hrs
12 Hrs
Recharge Volts =
12.0-16.0* VDC
12.0*V
Hold CV Chg VDC
03D Absorb Done
Time = 0.1-25.5 Hrs
≥
Level 4 [4]
2.0 Hrs
Amps = 0-250 ADC
≥
Level 4 [5]
20 ADC
SOC = 50-100%
≥
Level 4 [5]
100%
03E Max Charge Rate
10-100%
≥
Level 2
100%
0-100%
≥
Level 3
03F Max Charge Time OFF, 0.1-25.5 Hrs
≥
Level 4 [5]
12.0 Hrs
03G Final Charge
Stage
Multi, Float
≥
Level 4 [5]
Multi
Silent Rebulk = 12-16V*
≥
Level 4
12.0*V
03H EQ Reminder
Days
OFF, 1-255 Days
≥
Level 1
OFF
04
AGS
Setup
04A Gen Run VDC
Start Volts = OFF, 9.0-15.9*
≥
Level 1
11.5*V
Start Delay = 0-127s, 1-127m
120 Sec
Stop = 9.1-16.0*, Float
14.4*V
Stop Delay = 0-127s, 1-127m
120 Sec
04B Gen Run Time
OFF, ON – Start Time =
12:00A-11:45P
≥
Level 1
OFF
Stop Time = 12:00A-11:45P
12:00A
04C Gen Run Amps
Start Amps = OFF, 5-60A
≥
Level 4
OFF
Start Delay = 0-127s, 1-127m
120 Sec
Stop Amps = 4-59A
4A
Stop Delay = 0-127s, 1-127m
120 Sec
Custom