Appendix A – ME-ARC Compatibility Matrix
Page 127
Button
Features/Settings
Model/
Level
Required
Default
Main
Menu
Menu
Heading/Item
Selections/
Adjustments Range
METER
07 PT
Meters
07F Power to Bat
Now:
Read Only
displays
≥
Level 1
Read
Only
Life:
Reset:
07G Ground Fault
Read Only display
07H PT Data
PT Data
07I Clear PT Data
History
Clear PT History
07J PT Version
Read Only display
SETUP
01
System
Setup
01A Set Clock
Time = 12:00A - 11:59P
≥
Level 1
12:00A**
01B Screen Setup
Brightness = 0-100%
≥
Level 1
50%**
Contrast = 0-100%
100%**
Pwr Save = OFF, 1-60 Min
15 Min
01C Temp Display
Fahrenheit, Celsius
≥
Level 1
Fahren-
heit
01D Max Charge
Amps
OFF, 20-990 ADC
≥
Level 1
200 ADC
01E Link PT CHG
settings
YES, NO
≥
Level 1
YES
02
Invert
Setup
02A Search Watts
OFF, 5-50 Watts
≥
Level 1
5 Watts
02B LBCO Setting
9.0-12.2*VDC
≥
Level 2
10.0*V
02C AC In - Time
Connect Time = 12:00A - 11:45P
≥
Level 3
[1]
6:00A
6:00P
Disconnect Time = 12:00A - 11:45P
02D AC In - VDC
Connect Volts = 9.0-15.9*
≥
Level 3
[1]
11.0*V
Disconnect Volts = 9.1-16.0*
14.1*V
02E AC In - SOC
Connect SOC = 20%-99%
≥
Level 3
[6]
80%
Disconnect SOC = 21%-100%
100%
02F Power Up Always OFF, ON
≥
Level 1
OFF
03
Charger
Setup
03A AC Input Amps
AC1 Input Amps = 5-60
≥
Level 1
[1]
30A
AC2 Input Amps = 5-60
MSH-RE
only
20A
03B VAC Dropout
AC1 = 60-100 VAC, UPS Mode
U.S.
Models
80 VAC
AC2 = 60-100 VAC
MSH-RE
Models
70 VAC
110-190 VAC, UPS Mode
Export
models
150 VAC