Select a ground fault interrupter not affected by high frequencies. To prevent
malfunctions, the current should be 200mA or more and the operating time 0.1
second or more.
•
A
AC
C rre
ea
ac
ctto
orr
Install an AC reactor to connect to a power supply transformer of large capacity (600
kVA or more) or to improve the power factor on the power supply side.
•
N
No
oiis
se
e ffiilltte
err
Use a noise filter exclusively for the drive if radio noise generated from the drive
causes other control devices to malfunction.
CAUTION
Never connect a general LC/RC noise filter to the drive output circuit.
Do not connect a phase-advancing capacitor to the input/output sides or a
surge suppressor to the output side of the drive.
When a magentic contactor is installed between the drive and the motor, do
not turn it on or off during operation.
For more details on peripheral devices, refer to the GPD Price Book, or contact your
MagneTek representative.