Appendix 2. PERIPHERAL DEVICES
The following peripheral devices may be required to be mounted between the AC main
circuit power supply and the GPD 205 input terminals L1 (R), L2 (S) and L3 (T).
•
M
Mo
olld
de
ed
d--c
ca
as
se
e c
ciirrc
cu
uiitt b
brre
ea
ak
ke
err ((M
MC
CC
CB
B))
•
M
Ma
ag
gn
ne
ettiic
c c
co
on
ntta
ac
ctto
orr
Mount a surge protector on the coil. When using a magnetic contactor to start and
stop the drive, do not exceed one start per hour.
IMPORTANT: See C
CA
AU
UT
TIIO
ON
N on next page.
115 V
Model GPD205-
10P1
10P2
10P7
1001
Capacity (kVA)
0.3
0.6
1.1
1.9
Rated output current (A)
0.8
1.5
3
5
Rated input current (A)
3.2
6.0
12.0
20.0
MCCB rating
10A
10A
10A
15A
230 V
Model GPD205-
A0P1
A0P2
A0P7
A001
A002
Capacity (kVA)
0.3
0.6
1.1
1.9
2.6
Rated output current (A)
0.8
1.5
3
5
7
Rated input current (A)
0.9
1.7
3.3
5.5
7.7
MCCB rating
5A
5A
5A
10A
10A
460 V
Model GPD205-
B0P7
B0P7
B001
B003
Capacity (kVA)
0.9
1.4
2.6
3.7
Rated output current (A)
1.2
1.8
3.4
4.8
Rated input current (A)
1.9
2.6
4.5
7.0
MCCB rating
5A
5A
10A
10A
for more: efesotomasyon - Yaskawa drive