WARNING
Do not touch circuit components until main input power has been turned
OFF. Status indicator LEDs and Digital Operator display will be extinguished
when the DC bus voltage is below 50 VDC. Wait at least one additional
minute.
Do not connect or disconnect wires and connectors while the main input
power is turned on.
CAUTION
The GPD 205 leaves the factory with constants initialized for 2-Wire control
(when using external Run/Stop signals). Before using the initialization
function of constant
n01 , know your control wiring configuration:
8 = Factory 2-Wire Control Initialization (Maintained RUN Contact)
9 = Factory 3-Wire Control Initialization (Momentary START/STOP Contact)
Entering either Initialization code resets all constants to factory settings, and
automatically returns constant
n01 setting to “ 1 ”. If the GPD 205 is
connected for 3-Wire control and this constant is set to “ 8 ” (2-Wire Control
Initialization), the motor may run in reverse direction WITHOUT A RUN
COMMAND APPLIED. Equipment damage or personal injury may result.
CAUTION
Constant
n25 must be set to proper motor voltage. Drive leaves factory with
this constant set for “ 230 ” volts.
CAUTION
Always ground the GPD 205 using its ground terminal ( ) (near the main
circuit output terminals). See paragraph 1.4.1, “Grounding”.
Never connect main circuit output terminals T1 (U), T2 (V) & T3 (W) to AC
main circuit power supply.