Range: 30 - 200 (%)
n
n 3
3 5
5
A
Att S
Se
ett S
Sp
pe
ee
ed
d
Factory Setting: 160
This constant determines the actual GPD 205 output current level while operating at
set speed (frequency). Set in percent of GPD 205 rated output current (see
Appendix 1).
A setting of “ 200 ” disables
stall prevention at set speed.
During running at set speed, if
the output current exceeds
the value set in n
n 3
3 5
5 , the
drive will begin to decelerate.
When the output current goes
below the value set in n
n 3
3 5
5 ,
acceleration begins, up to the
set frequency.
C
Co
on
ns
stta
an
ntt M
Mo
om
me
en
ntta
arry
y P
Po
ow
we
err L
Lo
os
ss
s
Factory Setting: 0
n
n 3
3 6
6
F
Fu
un
nc
cttiio
on
n S
Se
elle
ec
cttiio
on
n
This constant determines how the momentary power loss ride-thru function of the
GPD 205 will operate.
Setting
Function
0
Operation during momentary power loss disabled
1
Operation during momentary power loss enabled —
0.5 sec. power loss ride-thru
( “
U u ” displayed during power loss)
2
Operation during momentary power loss enabled —
indefinite power loss ride-thru, provided control power
is maintained
( “
U u ” displayed during power loss; no fault signal is
output at control circuit terminals MA & MB or PA)
43
t
t
MOTOR
CURRENT
OUTPUT
FREQ.
Constant
n35
setting