Range: 0.0 - 25.5 (Amps)
n
n 3
3 1
1
Factory setting: see pg. 17
This constant should be set to the actual rated current value shown on the motor
nameplate. Make sure that the motor rated current is lle
es
ss
s tth
ha
an
n o
orr e
eq
qu
ua
all tto
o the
drive rated current shown in Appendix 1.
NOTE: Setting n
n 3
3 1
1 to “ 0.0 ” disables the motor overload protection function,
regardless of the setting of n
n 3
3 2
2 .
C
Co
on
ns
stta
an
ntt E
Elle
ec
cttrro
on
niic
c T
Th
he
errm
ma
all
Factory Setting: 0
n
n 3
3 2
2
M
Mo
otto
orr P
Prro
otte
ec
cttiio
on
n
Setting
Electronic Thermal Characteristics
0
General-purpose motor, standard rating (8 min.)
1
General-purpose motor, short-term rating (5 min.)
2
Blower-cooled motor, standard rating (8 min.)
3
Blower-cooled motor, short-term rating (5 min.)
4
Electronic thermal overload protection disabled
The GPD 205 protects against motor overload with a UL-recognized, built-in
electronic thermal overload relay.
The electronic thermal overload function monitors motor temperature, based on drive
output current and time, to protect the motor from overheating. When the electronic
thermal overload trips, an “ o
o L
L 1
1 ” error occurs, shutting OFF the drive output and
preventing excessive overheating in the motor. When operating with one drive
connected to only one motor, an external thermal relay is not needed. When
operating several motors with one drive, install a thermal overload relay on each
motor.
•
G
Ge
en
ne
erra
all--p
pu
urrp
po
os
se
e a
an
nd
d b
bllo
ow
we
err--c
co
oo
olle
ed
d m
mo
otto
orrs
s
Induction motors are classified as general-purpose or blower-cooled motors, based on
their cooling capabilities; the motor overload detection function operates differently,
as shown, for each of these two motor types.
40
for more: efesotomasyon - Yaskawa drive