Control Circuit Terminal Functions
N
NO
OT
TE
ES
S::
1
These inputs have factory settings based on 2-Wire reset.
For 3-Wire reset definitions, see Figure 1-6.
2
Factory setting is for 0-3V = 0-100% frequency. Can be set
for 0-10V = 0-100% output current; see page 46.
3
Multi-function open collector output is factory set for “Fault.”
For other settings, see page 32.
7
Type
Terminal
Terminal Name
Terminal Function
Signal Level
I
n
p
u
t
O
u
t
p
u
t
S
e
q
u
e
n
c
e
(1)
F
r
e
q
u
e
n
c
y
R
e
f
e
r
e
n
c
e
SF
Forward Run/Stop
Photocoupler
isolated
input;
24VDC
8mA
0 to 10VDC
2mA or less
Photocoupler
output;
48VDC
50mA or less
Forward run when closed,
stop when open
(1)
SR
Reverse Run/Stop
Reverse run when closed,
stop when open
(1)
S1
Multi-function contact
input 1
Factory setting is “Fault
Reset”
(1)
S2
Multi-function contact
input 2
Factory setting is “External
Fault (NO contact) input”
(1)
S3
Multi-function contact
input 3
Factory setting is “Multi-step
Speed Reference 1”
(1)
SC
Sequence common
Common terminal for
sequence inputs
FS
Frequency reference
power supply
+15 VDC
FR
Frequency reference
input
0 to 10 VDC (20 K
Ω
) or 4 to 20mA (250
Ω
)
FC
Frequency reference
input common
0V
AM
Analog monitor output
Factory setting is “Output
frequency”
0-3V = 0-100%
(2)
AC
Analog monitor output
common
0V
PA
Factory setting is “Fault”
(3)
PC
Open collector output
common
Open collector output
for more: efesotomasyon - Yaskawa drive