Observe the following while completing
interconnections:
•
Use only factory supplied installation instructions to install
optional dynamic braking resistors. Failure to do so may cause
equipment damage or personal injury.
•
Use 600V vinyl-sheathed lead (75°C copper wires) or equivalent.
Wire size should be determined by considering voltage drop of
leads. Recommended size is 18-14 AWG (0.75-2 mm
2
). Size of wire
must be suitable for Class 1 circuits.
•
Never connect AC main power to output terminals T1 (U), T2 (V)
and T3 (W).
•
Never allow wire leads to contact the GPD 205 enclosure. Short-
circuit may result.
•
Torque all main circuit M3.5 terminal screws to .70 lb-ft.
•
Never connect power factor correction capacitors or noise filter
to GPD 205 output.
•
Motor lead length should NOT EXCEED 328 feet (100 meters), and
motor wiring should be run in a separate conduit from the power
wiring.
4
NOT
ACCEPTABLE
CORRECT
CORRECT
Figure 1-4. Grounding of Three GPD 205s