5-23
Symptom
Content of the likely cause
Countermeasures
Reference
Unable to run/set
with Modbus
communication.
The changes on the communication
parameter are not reflected.
If the communication transmission speed selection
(C071), communication parity selection (C074), or
communication stop bit selection (C075) were
changed, restart the power or reset (Turn ON then
OFF on the RS terminal).
The primary/secondary run command
selection (A002/A202) is incorrect.
Set the primary/secondary run command selection
(A002/A202) to “03: Modbus communication”.
The primary/secondary frequency
command selection (A001/A201) is
incorrect.
Set the primary/secondary frequency command
selection (A001/A201) to “03: Modbus
communication”.
The communication speed setting is
incorrect.
Set the correct communication speed on the
communication transmission speed selection
(C071).
The station number setting is incorrect.
Or is overlapping.
Set the correct station number on the
communication station number selection (C072).
The communication parity setting is
incorrect.
Set the correct communication parity on the
communication parity selection (C074).
The communication stop bit setting is
incorrect.
Set the correct stop bit on the communication stop
bit selection (C075).
Incorrect wiring.
Route the wires properly to the RS+, RS-
terminal of the control circuit terminal block.
Incorrect address.
• Check that the coil address and register address
are correct, and that the value “
−
1” from the
register number is set.
• If the Modbus mapping function is being used,
check that the setting is correct, and fix
accordingly.
The circuit breaker
activates when
running the
inverter.
The leakage current of the inverter is
large.
Reduce the carrier frequency (b083).
Raise the sensitive current of the leakage breaker.
Or replace with circuit breaker with higher sensitive
current.
DC breaking does
not operate.
The DC breaking has not been set.
Set the DC breaking (A054).
The DC breaking time has not been set.
Set the DC breaking time (A055).
Trips with
insufficient voltage
(E09).
Voltage drop due to insufficient power
capacity.
Raise the power capacity.
Noise is observed
on television sets
and radio near the
inverter.
Noise emitted from the inverter.
Place the cables of the inverter as far as possible
from the television set and radio.
Optional units fault
(E60 to E68)
occurs.
The optional units detected a failure
and reported them.
Refer to the manuals of the optional units.
Inverter failure; the optional unit
connector is not operating normally.
If the issue cannot be solved on the optional unit
side, it may be a failure. If the issue cannot be
solved after checking the bad linkage and
contamination of the connection part, replace the
inverter.
Optional units fault
(E69) occurs.
Communication cannot be carried out
after the optional unit has been
detected. Optional unit may be loose.
Check for bad linkage, contamination of the
connection part of the optional unit connector.
Check that the terminal block cover of the inverter
and the cover of the optional unit are properly
linked, and that the screws are properly installed.
The endian function of the Modbus
mapping function is set improperly.
Set Modbus mapping endian selection (P400) to
“00: big endian”.
Содержание MK0003
Страница 2: ......
Страница 8: ...0 6...
Страница 12: ...1 4 2 DIMENSIONAL DRAWING OF OUTRIGGER WIDTH...
Страница 17: ...1 9 4 WORKING RADIUS LIFTING HEIGHT...
Страница 18: ...1 10 Working range diagram Outrigger extended to maximum Main boom 1 section...
Страница 19: ...1 11 Working range diagram Outrigger extended to maximum Main boom 2 sections...
Страница 20: ...1 12 Working range diagram Outrigger extended to maximum Main boom 2 5 sections...
Страница 21: ...1 13 Working range diagram Outrigger extended to maximum Main boom 3 sections...
Страница 22: ...1 14 Working range diagram Outrigger extended to minimum Main boom 1 section...
Страница 23: ...1 15 Working range diagram Outrigger extended to minimum Main boom 2 sections...
Страница 24: ...1 16 Working range diagram Outrigger extended to minimum Main boom 2 5 sections...
Страница 25: ...1 17 Working range diagram Outrigger extended to minimum Main boom 3 sections...
Страница 26: ...1 18 5 RATED TOTAL LOAD CHART...
Страница 32: ...2 4...
Страница 33: ...2 5 1 HYDRAULIC CIRCUIT DIAGRAM 200 1176600...
Страница 34: ...2 6...
Страница 35: ...2 7 2 HYDRAULIC PIPING DIAGRAM 2 1 CRANE ROTATING PART 200 1171800...
Страница 41: ...2 13 2 2 CONTROL LINE A...
Страница 43: ...2 15 2 3CONTROL LINE B Perform spiral winding on the entire perimeter of the hose of this part...
Страница 45: ...2 17 2 4 TRAVEL LINE...
Страница 47: ...2 19 2 5 OUTRIGGER LINE...
Страница 49: ...2 21 2 6 PT LINE 102 1152000 4...
Страница 69: ...2 41...
Страница 70: ...2 42...
Страница 71: ...2 43...
Страница 76: ...2 48 4 8 ENGINE ACCESSORIES 102 1149200...
Страница 90: ...2 62 7 2 INTERNAL STRUCTURE...
Страница 120: ...2 92 Part B Writing method for wire number Two places...
Страница 123: ...2 95 Figure 1 Index point Figure 2 Connection diagram...
Страница 166: ...2 138 15 4 APPEARANCE OF OUTRIGGER ON REAR LEFT SIDE 200 2167300...
Страница 173: ...2 145 17 ELECTRIC CIRCUIT DIAGRAM 200 1176500 01...
Страница 174: ...2 146 18 ELECTRIC SYSTEM 18 1 1 WIRE HARNESS OF MACHINE BODY 1 200 1172200 1...
Страница 176: ...2 148 18 1 2 WIRE HARNESS OF MACHINE BODY 2 200 1172200 2...
Страница 179: ...2 151 19 CONTROL ASSEMBLY 19 1 CONTROLLER 1 TTC60 Pin arrangement...
Страница 180: ...2 152 TTC60 I O...
Страница 181: ...2 153 2 TTC36X Pin arrangement...
Страница 182: ...2 154 TTC36X lower part I O...
Страница 209: ...2 181 19 2 5 LIST OF CONTROLLER INPUT MONITORING...
Страница 210: ...2 182 19 2 6 LIST OF CONTROLLER ANALOG INPUT OUTPUT MONITORING...
Страница 245: ...3 9 1 2 3 ANGLE METER 360 S200M3297000...
Страница 274: ...3 38...
Страница 293: ...4 19 8 SERVICE LOCATIONS...
Страница 294: ...4 20...
Страница 296: ...5 2 1 ELECTRICAL MOTOR UNIT ASSEMBLY Unit weight 180 kg...
Страница 299: ...5 5 1 1 POWER UNIT 1 Power unit cover 2 Electric motor 3 Coupling 4 Hydraulic pump Power supply box...
Страница 323: ...5 29 3 POWER SUPPLY BOX 1 Power supply box 2 Power supply box door 3 Door handle 4 Terminal block 5 Cable inserting hole...
Страница 324: ...5 30...
Страница 325: ...5 31 4 ELECTRICAL DIAGRAM S200M3122000 01...
Страница 326: ...5 32 S200M3122000 02...
Страница 336: ...6 8 1 3 2 INTERNAL STRUCTURE OF WINCH MOTOR...
Страница 345: ...6 17 4 WORKING RADIUS LIFTING HEIGHT OF ONE FALL WINCH...
Страница 348: ......