Reference Sheets for GRAFIK Eye Dimming Panel
ORANGE
BROWN
RED
BLUE
DH
1
SH
1
H
1
DH
2
SH
2
H
2
DH
3
SH
3
H
3
DH
4
SH
4
H
4
N
1
N
1
N
2
N
2
N
3
N
3
N
4
N
4
32
Look Inside a GP3 and 4
GP3 and GP4
GP3 and GP4 panels are very similar. GP3 panels have three
dimming circuits, with input circuit breakers provided, while a GP4
panel has four dimming circuits and no circuit breakers. One
difference is the way of wiring Neutrals in the GP3 and GP4 panels. A
GP3 panel has three terminals for all Neutrals bussed together. A GP4
panel has two Neutral terminal blocks provided for each circuit (one
for input and one for load).
Notes:
■
GP3 can be wired as 3Ø, 4 wire or 1Ø, 2 wire. If wiring is 1Ø, 2
wire, 3 #12 AWG (2.5mm
2
) must be spliced to the Hot/Live feed
wire.
CHOKE
DIMMER CARD
TRANSFORMER
DH
1
SH
1
H
1
DH
2
SH
2
H
2
DH
3
SH
3
H
3
CONTROL
WIRING
CHOKE
DIMMER CARD
TRANSFORMER
DIMMED HOT
NEUTRAL
INPUT FEED
INPUT CIRCUIT
BREAKER
GP3
GP4
CONTROL
WIRING
DIMMED
HOT
CIRCUIT
SELECTOR
CIRCUIT
SELECTOR
TYPICAL OF THREE
TYPICAL OF
FOUR
NEUTRAL
LOAD
16A MAX.
LOAD
16A MAX.
INPUT FEED
FOR CIRCUIT 4
Reference Sheet
■
All are in a NEMA Type 1 enclosure and provide protection of IP-
20.
■
120V and 277V panels are UL listed under UL file E42071 and
are CSA certified.
■
230V CE panels have been tested to IEC439-1. Rated isolation
voltage is 264Vac, rated short-time withstand current is 2000A
RMS for 1 second, and classification of short circuit protection is
100A gL fuse.
■
The input breaker of Circuit 1 supplies current to Load Circuit 1
and to the Control Wiring (2A draw max.)
GP3,4
ORANGE
BROWN
RED
BLUE
ORANGE
BROWN
RED
BLUE