Reference Sheets for GRAFIK Eye Dimming Panel
29
Circuit Selector Address
Warning:!
Each GP Panel must have a unique, specific
address. See Lutron's Load Schedule, Cabinet Detail
Report, or user setup software.
Assign Address to Circuit Selector
Address the Circuit Selector whenever it is to talk to a G6000
Controller or GRX-4500 Series Control Unit.
Caution!
Assigning an improper address to the Circuit
Selector can result in damage to the load.
A. To set or change the address, press and hold buttons 1 and 5
until the
SELECT VALUE
LED flashes once per second.
B. Press button 5 on circuit selector until “Ad” is displayed in the
Circuit
window.
If the
Value
window displays an address other than ‘–’, the
address has already been set (proceed to Step D).
C. Use button 3 or 4 to assign an address (1—512) to the Circuit
Selector. This address should match the address in the job
drawing.
D. Press and hold buttons 1 and 5 on the Circuit Selector until the
VIEW VALUE
LED lights.
Notes:
■
The
Value
window will display the software revision level of the
Circuit Selector 20 minutes after the last button press.
■
Panel addressing must be completed prior to transferring data
from LIAISON™ or the GRAFIK 6000 controller.
■
Mark addresses on a Circuit Directory for future reference.
■
If
'LC'
is displayed in the Circuit window, the circuit selection is
locked out. Contact the Lutron Field Service Department.
Circuit Selector
S
ELECT
V
ALUE
V
IEW
V
ALUE
S
ELECT
V
ALUE
D
ISPLAYED
Load Type (See Instructions)
Circuit Level
5
4
3
Link A
Link B
S
ELECT
C
IRCUIT
2
1
Circuit
Common
24VFW
MUX
MUX
Drain
Sense
1 2 3 4
D
5
Value
B
Comm
Drain
MUX
MUX
C
D
Link
A
Link
C
B
A, D