Reference Sheets for GRAFIK Eye Dimming Panel
33
Look Inside a GP8
through 24
Reference Sheet
GP8 through 24
The only difference among GP8, 12, 16, 20, and 24 panels is the
number of 16A dimmers (and associated components) in each.
Notes:
■
GP3 can be wired as 3Ø, 4 wire or 1Ø, 2 wire. If wiring is 1Ø, 2
wire, 3 #12 AWG (2.5mm
2
) must be spliced to the Hot/Live feed
wire.
■
All are in a NEMA Type 1 enclosure and provide protection of IP-
20.
...
...
...
DH
1
SH
1
H
1
DH
2
SH
2
H
2
DH
3
SH
3
H
3
TRANSFORMER
16A
CHOKE
CONTROL
WIRING
DIMMER
CARD
CIRCUIT
SELECTOR
GP8 through 24
NEUTRAL
HOT
NEUTRAL
BUS
MAIN
BREAKER
INPUT BREAKER
LOAD
16A MAX.
Note:
There is no Neutral bus on 230V or 240V panels. Neutral
terminals are included with the indexed load terminals.
2
3
C
21
1
5
17
22
2
6
9
14 18
23
3
7
10 12 15 19
24
4
8
11 13 16 20
FEED WIRE ENTRY
GP8 through 24 Components
FILTER (Chokes are located
behind the breaker and terminal
block pans)
LOAD CIRCUIT WIRE ENTRY
DIMMER CARDS
CIRCUIT SELECTOR
CONTROL WIRE ENTRY
GROUND (EARTH) BAR
INDEXED LOAD TERMINALS
NEUTRAL BUS
CONTROL BREAKER
CIRCUIT BREAKERS
MAIN LUGS, MAIN BREAKER,
OR ISO SWITCH
GP8 24
■
120V and 277V panels are UL listed under UL file E42071 and
are CSA certified.
■
230V CE panels have been tested to IEC439-1. Rated isolation
voltage is 264Vac, rated short-time withstand current is 2000A
RMS for 1 second, and classification of short circuit protection is
100A gL fuse.