Reference Sheets for GRAFIK Eye Dimming Panel
25
Save Options
Reference Sheet
The GRAFIK Eye 4000 Series Control Units allow selection of several
different Save Options. Follow these steps to access the Save
Options.
1. Enter setup mode
. Press and hold Scene 1 and OFF buttons
for about 3 seconds until scene LEDs start cycling.
2. Select
Sd
.
Press FADE
5
until Sd is displayed in the FADE
window.
3. Select Save Options
. Press MASTER
5
and
6
to select
between the Save Options:
Sd
Save by Default.
Changing a zone’s intensity level or
fade time permanently changes the preset scene. To
temporarily change a light level, see “How to adjust light
levels temporarily” on page 8.
Sb
Save by Button.
TEMPORARY ZONES LED is normally
ON and all intensity and fade changes are temporary unless
the TEMPORARY ZONES LED is turned OFF with the
TEMPORARY ZONES button.
Sn
Save Never.
TEMPORARY ZONES LED is permanently ON
and cannot be turned OFF. In this mode, all intensity
changes are temporary.
4S
Four Scenes.
This only allows the four Scene buttons,
OFF button, IR receiver and the MASTER
5
or
6
to
operate. All other buttons on the Control Unit are disabled.
bd
Button Disable.
All buttons on the Control Unit are
disabled. IR Receiver, and Wallstations are still functional.
(Setup mode is still accessible by repeating Step 1.)
4. Exit setup mode
. Press and hold Scene 1 and OFF buttons
until scene LEDs stop cycling.
FADE
TEMPORARY
MASTER
ZONES
ZONE 5
ZONE 6
M S
Enter (exit)
Setup Mode
Select Save
Option
Select Sd