Step by Step instructions for GRAFIK Eye Dimming Panel
12
Install Wallstations
and Activate Loads
STEP 7:
Install Wallstations
After wiring, setting address switches, and setting function switches,
mount the Wallstations. Refer to detailed mounting instructions
packaged with each control.
STEP 8:
Activate Loads in Bypass
A. Complete load wiring.
B. Check that the bypass jumpers are in place.
These jumpers protect the dimmers from faults and must be
used to check load wiring when it is installed or modified.
Warning!
For GP3 or GP4, the input breaker of Circuit
1 powers the control wiring as well as Circuit 1's
dimmer and load. Steps 8 and 9 should be performed
concurrently for these panels.
C. Turn circuit breaker 1 ON.
The load should energize, the breaker should not trip, and total
load current must be within the Circuit Breaker's limit and less
than 16A.
D. Repeat ‘C.’ for each circuit with completed load
wiring.
Warning!
DO NOT remove bypass jumpers at this time.
Caution!
For proper dimming performance fluorescent
lamps must be operated at full intensity for 100 hours
prior to dimming.
See Maintenance Reference sheet in the Reference
Section of this guide.
Note:
For those who purchased Start Up with their Lutron Dimming
System — you may want to stop here and have the Lutron Field
Engineer set-up the system. Please call for a Start Up visit at least
10 working days before your requested date.
AC RMS CURRENT
TERMINAL BLOCKS
Bypass Jumpers
LOAD CIRCUIT WIRING
FEED WIRING
CIRCUIT BREAKERS
WALLBOX
WALLSTATION
CONTROL MOUNTING
SCREWS
ADAPTER MOUNTING
SCREWS
FACEPLATE ADAPTER
FACEPLATE
CONTROL
LINK