Reference Sheets for GRAFIK Eye Dimming Panel
34
Ballast and Fixture Wiring
One Lamp
Two Lamps
Two Compact Fluorescent Lamps
Three Lamps
Notes:
■
Ballasts must be located so that the maximum case temperature
is less than 75 °C (167 °F) and the relative humidity is less than
90%, non-condensing.
■
Avoid situations where strong air drafts blow directly on bare
bulbs (minimum start temperature is 10 °C).
■
Good metal-to-metal contact between lamp pins and lamp holder
contacts is necessary for proper dimming performance. Knife-
edge sockets are recommended.
■
For those who purchased Start Up with their Lutron Dimming
System - you may want to stop here and have the Lutron Field
Engineer set-up the system. Please call for a Start Up visit at
least 10 working days before your requested date.
RED
TO DIMMING
PANEL
TO NEXT BALLAST
TO NEXT BALLAST
TO NEXT BALLAST
TO NEXT BALLAST
DIMMED HOT - ORANGE
SWITCHED HOT - BLACK
NEUTRAL - WHITE
TO DIMMING
PANEL
TO DIMMING
PANEL
TO DIMMING
PANEL
Hi-lume FDB/
Eco-10 BALLAST
BLUE
Mount to
Grounded Fixture
LAMP
LAMP
LAMP
RED
YELLOW
BLUE
Hi-lume FDB/
Eco-10 BALLAST
Mount to
Grounded Fixture
BLUE
BLUE
RED
RED
YELLOW
YELLOW
Hi-lume FDB/
Eco-10 BALLAST
Mount to
Grounded Fixture
RED
YELLOW
BLUE
LAMP
LAMP
LAMP
Hi-lume FDB/
Eco-10 BALLAST
Mount to
Grounded Fixture
BLUE/WHITE
■
Compact Fluorescent lamps must be 4 pin.
■
Ballast cases and fixtures must be earth grounded.
■
Yellow and blue w/white trace leads, from the ballast should be
kept as short as possible.
■
Ballasts are not designed for remote mounting. Total length of
wire from the ballast to the lamp socket is not to exceed 7 ft.
(2.1 m) for T8, T12, and not to exceed 3 ft. (0.9 m) for T4, T5.
■
240V Ballasts have different wire colors-follow the label on each
individual ballast.
Fluorescent Wiring
Information
Reference Sheet
DIMMED HOT - ORANGE
SWITCHED HOT - BLACK
NEUTRAL - WHITE
DIMMED HOT - ORANGE
SWITCHED HOT - BLACK
NEUTRAL - WHITE
DIMMED HOT - ORANGE
SWITCHED HOT - BLACK
NEUTRAL - WHITE