45
6
Gas connections
(continued)
Gas pressure
The gas pressure must remain between 4 inches w.c. (natural),
8 inches w.c. (LP) minimum and 14 inches w.c. (natural and
LP) maximum during stand-by (static) mode and while in
operating (dynamic) mode. If a gas pressure regulator is used,
it must be a minimum of 10 feet from the Shield water heater.
It is very important that the gas line is properly purged by the
gas supplier or utility company. Failure to properly purge the
lines or improper line sizing, will result in ignition failure.
The problem is especially noticeable in NEW LP installations
and also in empty tank situations. This can also occur when
a utility company shuts off service to an area to provide
maintenance to their lines.
A
LOOSEN THE SET SCREW ONE (1)
FULL TURN AND PLACE THE MANOMETER
TUBING OVER THE
PRESSURE TRAP
DETAIL A
DIR #2000586425
Figure 6-4
Inlet Gas Supply Check - Models 125-- 285
A
LOOSEN THE SET SCREW ONE (1)
FULL TURN AND PLACE THE MANOMETER
TUBING OVER THE PRESSURE TAP
DETAIL A
DIR #2000586431
Figure 6-5
Inlet Gas Supply Check - Model 400
A
LOOSEN THE SET SCREW ONE (1)
FULL TURN AND PLACE THE MANOMETER
TUBING OVER THE PRESSURE TAP
DETAIL A
DIR #2000586420
Figure 6-6
Inlet Gas Supply Check - Model 500
DO NOT attempt to measure gas valve
outlet pressure. The gas valve is factory-set
for the correct outlet pressure. This setting
is suitable for natural gas and propane
(when configured for LP), requiring no
field adjustment. Attempting to measure
the gas valve outlet pressure could
result in damage to the valve, causing
potential severe personal injury, death, or
substantial property damage.
Failure to follow all precautions could
result in fire, explosion, or death!
⚠
WARNING
⚠
WARNING
Gas valve replacement
The gas valve MUST NOT be replaced with a conventional
gas valve under any circumstances. As an additional safety
feature, this gas valve has a flanged connection to the venturi
and blower.
17. Check burner performance by cycling the system while
you observe burner response. The burner should ignite
promptly. Flame pattern should be stable. Turn system
off and allow burner to cool, then cycle burner again to
ensure proper ignition and flame characteristics.
Installation & Service Manual
Содержание Shield SWA150
Страница 53: ...53 Figure 9 2 Operating Instructions Models 125 285 9 Start up continued Installation Service Manual ...
Страница 54: ...54 Figure 9 3 Operating Instructions Models 400 500 9 Start up Installation Service Manual ...
Страница 82: ...82 Notes ...
Страница 83: ...83 Notes ...
Страница 84: ...Revision Notes Revision A PCP 3000038210 CN 500026403 initial release MM 100329111_DIR 2000585724 Rev A 04 20 ...