Start-up
Installation & Service Manual
Setup wizard
The Shield water heater control has a Setup Wizard feature
that can be used to help with the initial start-up of the unit.
This Setup Wizard will walk an installer through the most
commonly required parameters.
The Setup Wizard is automatically accessed the first time the
unit is powered up from the factory and will allow setting
of certain parameters without the need to enter the installer
password. Once the Setup Wizard is completed or canceled,
it can only be accessed again by going through the Installer
Menu.
Figure 9-6
Installer Menu
Button functions in the setup wizard
▲/▼
- Change value of current parameter
►
- Move to the next parameter or finish Setup
Wizard on last parameter
◄
- Save changes and exit the Setup Wizard. This
will bypass the remaining parameters in the
Wizard.
To exit the menu without saving changes, you must cycle
power to the unit before exiting the menu.
Parameters in the setup wizard
- TEMPERATURE UNITS
• Controls the units in which all temperature will
be displayed.
• Range: °F – °C
• Default: °F
-
TANK SETPOINT
• Target water temperature for the tank thermostat.
The electronic control senses the tank temperature
and regulates water heater ignition and firing rate
to achieve the target temperature.
• Range: 60°F - 180°F
• Default: 140°F
-
TANK SETPOINT DIFFERENTIAL
• Number of degrees below which the tank thermostat
must fall for the electronic control to begin
firing the heater to achieve the target temperature.
See "Tank Setpoint Differential" for information
about the Tank Setpoint Differential feature and its
setup.
-
TIME / DATE
• The water heater control uses an internal clock
for the night setback feature and for logging events.
For these features to work properly, the clock must
be set when the water heater is first installed or when
the water heater has been powered off for more
than 15 minutes. Note that the internal clock does
not adjust for Daylight Savings Time and therefore,
will require a manual adjustment.
-
NIGHT SETBACK
• This value represents the number of degrees by
which the tank setpoint will be reduced while the
Night Setback feature is active. See the Night
Setback section of this manual for more information
about the Night Setback feature and its setup.
Содержание Shield SWA150
Страница 53: ...53 Figure 9 2 Operating Instructions Models 125 285 9 Start up continued Installation Service Manual ...
Страница 54: ...54 Figure 9 3 Operating Instructions Models 400 500 9 Start up Installation Service Manual ...
Страница 82: ...82 Notes ...
Страница 83: ...83 Notes ...
Страница 84: ...Revision Notes Revision A PCP 3000038210 CN 500026403 initial release MM 100329111_DIR 2000585724 Rev A 04 20 ...