71
12
Troubleshooting
(continued)
Table 12E
Troubleshooting Chart - Noisy System
FAULT
CAUSE
CORRECTIVE ACTION
Noisy
Operation
- Supply gas problem. Natural gas pressures
should be between 4 inches w.c. and
14 inches w.c. LP gas pressures should
be between 8 inches w.c. and 14 inches w.c.
• Refer to Section 6 - Gas Connections for detailed
information concerning the gas supply.
- Gas/air mixture problem.
• Refer to the Gas Valve Adjustment Procedure on
page 79 of this manual for the proper gas valve setting.
Verify that the vent/air intake lengths do not exceed the
maximum listed in the General Venting section.
- Dirty/damaged burner.
• Refer to page 66 in this manual for the burner removal
and inspection procedure. Clean or replace the burner
as necessary.
- Low water flow through the heat exchanger. • Very pump operation.
- Air in the piping system.
• Properly purge all air from the piping system.
No Pump
Operation
- Blown fuse.
• Replace fuse F5 on the control board, see page 68 of
this manual.
- Faulty pump.
• Replace pump.
- Faulty pump relay.
• Replace pump relay.
- Internal fault on control board.
• Replace main control board.
Relief Valve
Opening
- System pressure exceeds relief valve
setting.
• Lower the system pressure below the 150 PSI rating of
the supplied relief valve.
Installation & Service Manual
Содержание Shield SWA150
Страница 53: ...53 Figure 9 2 Operating Instructions Models 125 285 9 Start up continued Installation Service Manual ...
Страница 54: ...54 Figure 9 3 Operating Instructions Models 400 500 9 Start up Installation Service Manual ...
Страница 82: ...82 Notes ...
Страница 83: ...83 Notes ...
Страница 84: ...Revision Notes Revision A PCP 3000038210 CN 500026403 initial release MM 100329111_DIR 2000585724 Rev A 04 20 ...