25
3
Sidewall direct
venting
(continued)
Installation & Service Manual
Figure 3-3A
Direct Vent Terminal Clearances
Canadian Installations¹
US Installations²
A =
Clearance above grade, veranda, porch,
deck, or balcony
12 in (30 cm)
12 in (30 cm)
B =
Clearance to window or door that may
be opened
6 in (15 cm) for appliances < 10,000 Btuh
(3 kW), 12 in (30 cm) for appliances >
10,000 Btuh (3 kW) and < 100,000 Btuh
(30 kW), 36 in (91 cm) for appliances >
100,000 Btuh (30 kW)
6 in (15 cm) for appliances < 10,000 Btuh
(3 kW), 9 in (23 cm) for appliances >
10,000 Btuh (3 kW) and < 50,000 Btuh (15
kW), 12 in (30 cm) for appliances > 50,000
Btuh (15 kW)
C =
Clearance to permanently closed
window
*
*
D =
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 ft (61 cm) from
the center line of the terminal.
*
*
E =
Clearance to unventilated soffit
*
*
F =
Clearance to outside corner
*
*
G =
Clearance to inside corner
*
*
H =
Clearance to each side of center line
extended above meter / regulator
assembly
*
*
I =
Clearance to service regulator vent
outlet
Above a regulator within 3 ft (91 cm)
horizontally of the vertical center line of the
regulator vent outlet to a maximum vertical
distance of 15 ft (4.5 m)
*
Table 3B
Direct Vent Terminal Clearances
Содержание Shield SWA150
Страница 53: ...53 Figure 9 2 Operating Instructions Models 125 285 9 Start up continued Installation Service Manual ...
Страница 54: ...54 Figure 9 3 Operating Instructions Models 400 500 9 Start up Installation Service Manual ...
Страница 82: ...82 Notes ...
Страница 83: ...83 Notes ...
Страница 84: ...Revision Notes Revision A PCP 3000038210 CN 500026403 initial release MM 100329111_DIR 2000585724 Rev A 04 20 ...