70
12
Troubleshooting
Table 12B -
Inlet Tank Sensor Resistance vs. Temperature
Temperature °F
Resistance
W
Temperature °F
Resistance
W
50
18,780
158
1,990
68
12,263
176
1,458
86
8,194
194
1,084
104
5,592
212
817
122
3,893
--
--
140
2,760
--
--
Table 12D -
Flue Temperature Sensor Resistance vs. Temperature
Temperature °F
Resistance
W
Temperature °F
Resistance
W
68
14,773
176
1,707
86
9,804
194
1,266
104
6,652
212
952
122
4,607
230
726
140
3,252
248
560
158
2,337
--
--
Checking temperature sensors
The water heater temperature sensors (inlet water, outlet water, tank water, and flue) are all resistance type devices. The following
tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a
known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor.
Installation & Service Manual
Table 12C -
Outlet Water Sensor Resistance vs. Temperature
S1a
(Wire Color - R/BK and Y)
S1b
(Wire Color - G and Y)
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
50
19,553
158
2,004
50
40,030
158
3,478
68
12,690
176
1,464
68
25,030
176
2,492
86
8,406
194
1,084
86
16,090
194
1,816
104
5,715
212
816
104
10,610
212
1,344
122
3,958
122
7,166
140
2,786
140
4,943
Содержание Shield SWA150
Страница 53: ...53 Figure 9 2 Operating Instructions Models 125 285 9 Start up continued Installation Service Manual ...
Страница 54: ...54 Figure 9 3 Operating Instructions Models 400 500 9 Start up Installation Service Manual ...
Страница 82: ...82 Notes ...
Страница 83: ...83 Notes ...
Страница 84: ...Revision Notes Revision A PCP 3000038210 CN 500026403 initial release MM 100329111_DIR 2000585724 Rev A 04 20 ...