31
Sidewall termination – optional concentric vent
Figure 3-9
Concentric Vent Dimensional Drawing -
Models 125 -- 200 / 100140480
Instead of cementing the smaller pipe
to the rain cap, a field-supplied stainless
steel screw may be used to secure the
two (2) components together when
field disassembly is desired for cleaning
(see FIG. 3-11).
When using the alternate screw assembly
method, drill a clearance hole in the rain
cap and a pilot hole in the vent pipe for
the screw size being used. Failure to drill
adequate holes may cause cracking of
PVC components, allowing combustion
products to be recirculated. Failure
to follow this warning could result in
personal injury or death.
Do not operate the appliance with
the rain cap removed or recirculation
of combustion products may occur.
Water may also collect inside the larger
combustion air pipe and flow to the
burner enclosure. Failure to follow this
warning could result in product damage
or improper operation, personal injury,
or death.
Figure 3-11
Rain Cap to Vent Pipe Alternate Assembly
6. Install the Y concentric fitting and pipe assembly through
the structure’s hole.
Do not allow insulation or other materials to
accumulate inside the pipe assembly when
installing through the hole.
7. Install the rain cap and small diameter pipe assembly into
the Y concentric fitting and large pipe assembly. Ensure
small diameter pipe is bottomed and cemented in the Y
concentric fitting for #100140480 installations and fastened
tightly into the rubber adapter for #100140484 installations.
8. Secure the assembly to the structure as shown in FIG. 3-12
using field-supplied metal strapping or equivalent support
material.
Ensure termination location clearance
dimensions are as shown in FIG. 3-6.
NOTICE
⚠
WARNING
⚠
WARNING
NOTICE
NOTICE
NOTICE
Figure 3-10
Concentric Vent Dimensional Drawing -
Models 285 -- 500 / 100140484
If assembly needs to be extended to allow
sidewall thickness requirement, the two (2)
pipes supplied in the kit may be replaced by
using the same diameter, field-supplied SDR-
26 PVC (D2241) pipe for 100140480 and
standard schedule 40 PVC for 100140484.
Do not extend dimension D* more than 60
inches (see FIG.’s 3-9 and 3-10).
If assembly depth needs to be reduced,
dimension D can be as short as possible.
NOTICE
"B" DIA. PVC
VENT / EXHAUST
"A"
"H" DIA.
"D"
"E"
"F"
"G"
3"
(76 MM)
A
B
C
D
E
F
G
H
60"
4"
6"
21 1/8"
10"
7 5/8"
3"
6 5/8"
"C" DIA.
"B" DIA.
(1524 MM)
(102 MM)
(152 MM) (537 MM) (254 MM) (194 MM) (76 MM)
(168 MM)
3
Sidewall direct venting
(continued)
Installation & Service Manual
Содержание Shield SWA150
Страница 53: ...53 Figure 9 2 Operating Instructions Models 125 285 9 Start up continued Installation Service Manual ...
Страница 54: ...54 Figure 9 3 Operating Instructions Models 400 500 9 Start up Installation Service Manual ...
Страница 82: ...82 Notes ...
Страница 83: ...83 Notes ...
Страница 84: ...Revision Notes Revision A PCP 3000038210 CN 500026403 initial release MM 100329111_DIR 2000585724 Rev A 04 20 ...