17
2
General venting
(continued)
Installation & Service Manual
Requirements for installation in
Canada
1. Installations must be made with a vent pipe system
certified to ULC-S636.
2. The first three (3) feet of plastic vent pipe from the
appliance flue outlet must be readily accessible for visual
inspection.
3. The components of the certified vent system must not be
interchanged with other vent systems or unlisted
pipe/fittings. For concentric vent installations, the inner
vent tube must be replaced with field supplied certified vent
material to comply with this requirement.
4. The 3" Concentric Vent Kit available from Lochinvar (see
Section 3 –
Sidewall Termination – Optional Concentric
Vent
) and the 3" Concentric Vent Kit available from IPEX
are both approved for use on the Shield water heater. Both
kits are listed to the ULC-S636 standard for use in Canada.
Minimum / Maximum allowable
combustion air and vent piping lengths
are as follows:
Combustion Air
= 12 equivalent feet minimum / 150
equivalent feet maximum
Vent
= 12 equivalent feet minimum / 150 equivalent feet
maximum
The appliance output rating will reduce
by up to 1.0% for each 25 feet of vent
length.
NOTICE
Table 2B
Concentric Vent Kit
Equivalent Vent Lengths
Sizing
The Shield water heater uses model specific combustion air
intake and vent piping sizes as detailed in Table 2A-1 below.
Table 2A
Air Intake/Vent Piping Sizes
NOTICE
Model
Air Intake
Vent
125 -- 200
3 inches
3 inches
285 -- 500
4 inches
4 inches
Model
Kit Number
Equivalent
Vent Length
125 -- 200
100140480
3 feet
285
100140484
3 feet
400
100140484
5 feet
500
100140484
30 feet
Increasing or decreasing combustion air
or vent piping sizes is not authorized.
When determining equivalent combustion air and vent
length, add 5 feet for each 90° elbow and 3 feet for each
45° elbow.
EXAMPLE:
20 feet of PVC pipe + (4) 90° (2)
45° (1) concentric vent kit (100140480) = 49
equivalent feet of piping.
Содержание Shield SWA150
Страница 53: ...53 Figure 9 2 Operating Instructions Models 125 285 9 Start up continued Installation Service Manual ...
Страница 54: ...54 Figure 9 3 Operating Instructions Models 400 500 9 Start up Installation Service Manual ...
Страница 82: ...82 Notes ...
Страница 83: ...83 Notes ...
Страница 84: ...Revision Notes Revision A PCP 3000038210 CN 500026403 initial release MM 100329111_DIR 2000585724 Rev A 04 20 ...