72
12
Troubleshooting
Table 12F
Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
Installation & Service Manual
FAULT
DESCRIPTION
CORRECTIVE ACTION
MEMORY
ERROR
The control module has detected parameter
settings that are corrupted.
• Replace control module.
FAN SPEED
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The actual fan RPM is outside of the tolerance
of the fan speed RPM target.
• Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 2 - General Venting for
proper lengths.
• Check for obstruction or blockage in the vent/air
intake pipes or at terminations.
• Check the wiring connections at the fan and at the
main control board.
• Replace the fan.
• Replace the main control board.
Blown fuse.
• Replace fuse F2 on the control board, see page 68
of this manual.
Flow Switch/
LWCO
(will require a manual
reset once condition has
been corrected. Press
the RESET button on the
SMART SYSTEM display
to reset.)
The low water cutoff (LWCO) is not making.
• Check water heater pump operation on a call for
heat.
• Check for closed valves or obstructions in the water
heater piping.
• Verify system is full of water and all air has been
purged from the system.
• Check for a loose or misplaced jumper if flow switch
is not installed.
• Replace LWCO.
Blown fuse.
• Replace fuse F3 on the control board, see page 68
of this manual.
FLAME
SEQUENCE
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The flame detector circuit is seeing a flame
signal when the gas valve is OFF.
• Verify flame is not present. If present, turn off gas
supply and replace gas valve.
• Check supply voltage for proper polarity.
• Check external wiring for voltage feedback.
• Check the flame rod and make sure it is clean.
• Check the internal wiring for bad connections.
• Replace main control board.
Содержание Shield SWA150
Страница 53: ...53 Figure 9 2 Operating Instructions Models 125 285 9 Start up continued Installation Service Manual ...
Страница 54: ...54 Figure 9 3 Operating Instructions Models 400 500 9 Start up Installation Service Manual ...
Страница 82: ...82 Notes ...
Страница 83: ...83 Notes ...
Страница 84: ...Revision Notes Revision A PCP 3000038210 CN 500026403 initial release MM 100329111_DIR 2000585724 Rev A 04 20 ...