104
Display message
F15
C l i x o n F a u l t
p u m p o n
9 9 9 , 5 h r s
Reason:
Heat exchanger fuse exceeded maximum value.
Cause:
The thermal fuse of the heat exchanger has opened permanently.
Corrective action:
Switch off the electrical power and gas supply and contact supplier.
Display message
F16
F l o w R e t u r n d t
f a u l t
p u m p o n
9 9 9 , 5 h r s
Reason:
Temperature difference between flow and return exceeds limitation value, or
'Heatexchang at Risk' has occurred 3 times.
Cause:
The water flow through the unit is too low.
Corrective action:
Check functioning of the pump.
Check/open all valves that might restrict the water flow through the unit.
Check for an external system pump that influences the flow through the unit.
Check if the system resistance exceeds the spare capacity of the unit pump.
Make sure the heat exchanger is clean. Heat exchanger fouling (partly blockage) will increase the resistance
causing the water flow to drop.
For
F16
see also
Flow Monitoring
Display message
F17
W a t e r h i g h
l i m i t
p u m p o n
9 9 9 , 5 h r s
Reason:
Maximum thermostat exceeds limitation value.
Cause:
The water flow is restricted.
Corrective action:
Check functioning of the pump.
Check/open all valves that might restrict the water flow through the unit.
Check for an external system pump that influences the flow through the unit.
Check if the system resistance exceeds the spare capacity of the unit pump.
Содержание EcoForce EF100
Страница 2: ...2 ...
Страница 11: ...11 3 1 4 Cascade frames Frames are available to mount up to 4 EcoForce water heaters if required ...
Страница 24: ...24 ...
Страница 25: ...25 ...
Страница 26: ...26 ...
Страница 30: ...30 ...
Страница 31: ...31 ...
Страница 32: ...32 ...
Страница 33: ...33 ...
Страница 119: ...119 ...
Страница 120: ...120 ...