38
This appliance can operate on a U-Duct common flue system. The maximum lengths for the interconnecting flue can be calculated using the
information in Section 8.8.2:
Concrete components of the U-Duct must meet the requirements of BS EN 1858
EF 58
EF80
EF100
EF120
EF150
EF180
Flue Gas Mass Rate (G20) 96%
(g/sec)
22.6
29.8
37.1
45.1
55.6
67.3
Flue Gas Mass Rate (G20) 25%
(g/sec)
5.7
7.5
9.3
11.3
13.9
16.8
Flue Gas Mass Rate (G31) 96%
(g/sec)
23.2
30.6
38.8
46.2
57.0
69.0
Flue Gas Mass Rate (G31) 25%
(g/sec)
5.8
7.7
9.7
11.6
14.3
17.3
8.12.1
Flue gas mass rates
C
OMMON
F
LUE
S
YSTEMS
The EF Water heater can be installed on to a common flue system if required. The common flue system should be sized to operate under a
negative pressure of -0.03 to -0.10 mbar.
If a positive pressure common flue system is to be used, a proprietary recirculation prevention device must be installed at the flue spigot of
each Water heater to prevent products of combustion from re-entering the plant room.
A cascaded common flue system which operates on a positive pressure is available from Lochinvar Limited. Further details can be found in
the Cascade Flue Systems guide, available from
www.lochinvar.Limited.uk
.
F
LUE
T
ERMINAL
G
UARDING
If a Vertical flue terminal is to be fitted less than 2 metres from ground level or in a location where it can be touched from a window, door or
balcony, a terminal guard must be fitted.
The terminal guard should be positioned centrally around the terminal and secured using appropriate wall fixings.
C
ONDENSATE
D
RAIN
For flue runs of less than 6 metres, provided that the flue system rises at an angle of at least 3
(50mm per metre), no additional condensate
drain will be required. Failure to provide an adequate rise in the flue system may lead to pooling of condensate which may lead to premature
failure of the flue system.
If the flue run is greater than 6 metres, it is recommended that an inline condensate drain and trap be fitted. The condensate trap should be
connected to a suitable drainage system as described in Section 6.2
C63
C
ERTIFIED
F
LUE
S
YSTEMS
In general Water heaters are certified with their own purpose supplied Concentric or Twin Pipe flue systems, C63 certified appliances allow
the installer to use other flue systems when installing the Water heater however they must be of a suitable minimum standard as per Table
8.16.1
CE string
flue gas
material
Eu
ro
pea
n
st
an
dar
d
Tem
per
a-
tu
re
class
Pr
es
su
re c
las
s
Resis
tan
ce
to
co
nd
en
sa
te
Co
rr
osio
n
res
ist
an
ce
class
M
et
al:
lin
er
sp
ec
ifica
tio
ns
So
ot
fir
e
res
ist
an
ce
class
Dist
an
ce
to
co
m
bu
st
ib
le
m
at
er
ial
Plas
tics
:
lo
ca
tio
n
Plas
tics
:
fir
e
beh
av
io
ur
Plas
tics
:
en
clo
su
re
min. eis PP
EN 14471
T120
P1
W
1
O
30
I of E
C/E
L
min. eis RVS
EN 1856-1
T120
P1
W
1
L20040
O
40
8.16.1
C63 flue system specification
Material
Water heater
d
nom mm
D
outside mm
d
inside mm
L
insert mm
SS
EF80
80
80 +0,3/ -0,7
81 +0,3/ -0,3
50 +2/ -2
SS
EF100-EF120
100
100 +0,3/ -0,7
101 +0,3/ -0,3
50 +2/ -2
SS
EF150-EF180
130
130 +0,3/ -0,7
131 +0,5/ -0,5
50 +2/ -2
PP
EF80-EF80
80
80 +0,6/ -0,6
50 +20/ -2
PP
EF100-EF120
100
100 +0,6/ -0,6
50 +20/ -2
PP
EF150-EF180
130
130 +0,9/ -0,9
50 +20/ -2
Aluminium flue pipe must not be used on this appliance as it may lead to premature failure of the heat exchanger
and will invalidate the warranty.
Содержание EcoForce EF100
Страница 2: ...2 ...
Страница 11: ...11 3 1 4 Cascade frames Frames are available to mount up to 4 EcoForce water heaters if required ...
Страница 24: ...24 ...
Страница 25: ...25 ...
Страница 26: ...26 ...
Страница 30: ...30 ...
Страница 31: ...31 ...
Страница 32: ...32 ...
Страница 33: ...33 ...
Страница 119: ...119 ...
Страница 120: ...120 ...