99
Display message
F1
R e t u r n h i g h T e m p
p u m p o n
9 9 9 , 5 h r s
Reason:
Maximum return temperature exceeds limit value.
Cause:
System that pre-heats the water heater return temperature too much/high.
Corrective action:
Reduce pre heat temperature of external heat source.
Cause:
The need for heat in the system suddenly drops causing hot return water to the water heater.
Corrective action:
Dampen external heating system control to prevent sudden water heater temperature rise.
Display message
F3
R e t u r n s e n s o r e r r o r
p u m p o n
9 9 9 , 5 h r s
Reason
Return sensor is not detected by the water heater PCB.
Cause:
Bad wiring/connection in the return sensor circuit.
Corrective action:
Check for loose wiring/connections in the return sensor circuit.
Cause:
Bad temperature sensor causing a fault signal.
Corrective action:
Replace return sensor.
Display message
F6
F l u e s e n s o r e r r o r
p u m p o n
9 9 9 , 5 h r s
Reason
Flue sensor is not detected by the water heater PCB.
Cause:
Bad wiring/connection in the flue gas sensor circuit.
Corrective action:
Check for loose wiring/connections in the flue gas sensor circuit.
Cause:
Bad temperature sensor causing a fault signal.
Corrective action:
Replace flue gas sensor.
Содержание EcoForce EF100
Страница 2: ...2 ...
Страница 11: ...11 3 1 4 Cascade frames Frames are available to mount up to 4 EcoForce water heaters if required ...
Страница 24: ...24 ...
Страница 25: ...25 ...
Страница 26: ...26 ...
Страница 30: ...30 ...
Страница 31: ...31 ...
Страница 32: ...32 ...
Страница 33: ...33 ...
Страница 119: ...119 ...
Страница 120: ...120 ...