74
Menu D: General
D 7 c o n f i g
Function for the setting of the water pressure.
Up to 4 bar a sensor is used, up to 6 bar a switch.
0 = off
1 = sensor
2 = switch
Menu D: General
D 8 g a s t y p e
Function to select the gas type
0 = standard
1 = G31*
2 = B/P G30*/G31*
* (cf. EN437)
Menu D: General
D 9 c o n f i g
Function for setting the 'soft start' option
0 = normal start-up
1 = reduced fan ramp-up speed (I)
2 = reduced fan ramp-up speed (II)
Menu D: General
D A c o n f i g
Function: Pump mode
0 = normal
1 = relay 1, connector 19 and 20 (lock-out)
2 = relay 2, connector 21 and 22 (burner burning)
3 = relay 3, connector 23 and 24 (heat demand)
4 = Do not use (reserved for future applications).
The Screen Text on these pages show
Parameters used on our EF water heater
and also our CPM Boilers. Certain
functions may not apply to the appliance
you are working on. If there is any doubt
contact Lochinvar Limited.