118
R
EFILLING
T
HE
S
YSTEM
1.
Close the drain valve on the storage vessel.
2.
Open a hot water fixture to allow air to escape.
3.
Open the cold water supply to water heating system and allow it to fill.
4.
Isolate the gas supply to the heater and reinstate the electrical supply.
5.
Once there is no air left in the heat exchanger (e.g. no air bleeding from the auto air vent), follow the lighting instructions as
detailed in
PROCEDURE FOR INITIAL LIGHTING
.
6.
Check for water leakage.
O
THER
C
HECKS
25.12.1
Relief valves (if fitted)
At least once a year, the temperature and pressure relief valve and safety valve should be checked to ensure that they are in operating
condition. To check each valve, lift the lever or turn the screw cap at the end of the valve several times. The valve should operate freely and
seat properly.
If water does not flow, remove and inspect for obstructions or corrosion. Replace with a new valve of the recommended size as necessary.
25.12.2
Flue system
Examine the exhaust and air intake system at least once a year. Points of inspection are as follows:
1.
Check for obstructions and/or deterioration of flue piping and terminal. Replace immediately where needed.
2.
Check the terminal for any foreign material and remove as necessary.
3.
Check all flue system connections for leakage and reseal as required.
4.
Check that ventilation grilles comply with current regulations.
ERP SPECIFICATION DATA SHEET
Water Heater Type:
EF80
EF100
EF120
EF150
EF180
Manufacturer
Lochinvar Limited
Load Profile
XXL
XXL
XXL
3XL
3XL
Energy Efficiency
%
86.0%
86.3%
85.9%
89.0%
88.6%
Daily Electricity Consumption
Qelec
27.9
27.82
27.97
51.92
52.16
Daily Fuel Consumption
Qfuel
0.245
0.242
0.24
0.24
0.235
Mixed water V40 @40
o
C
litre
*
*
*
*
*
Emissions of Nitrogen Oxides (EN155021:2012+A1:2015))
mg/kwh
46
40
45
41
44
Sound Power Level (EN 15036-1:2006)
LWA(db)
67
65
62
66
69
* EcoForce wall mounted water heaters must be combined with one or more direct storage vessels The Efficiency and V40 litre is
dependent upon:
The number and type of water heaters
the number and size of buffer vessels used
the length of the interconnecting pipework
insulation type used
USER INSTRUCTIONS
Once the installation and commissioning is complete, the equipment owner or their representative should be made aware of the operation of
the appliance and its safety devices. A practical demonstration should be given describing each functional step. Incorrect use may result in
injury and will also invalidate the warranty. The installers guide should be handed over and kept in a safe place for easy reference.
Содержание EcoForce EF100
Страница 2: ...2 ...
Страница 11: ...11 3 1 4 Cascade frames Frames are available to mount up to 4 EcoForce water heaters if required ...
Страница 24: ...24 ...
Страница 25: ...25 ...
Страница 26: ...26 ...
Страница 30: ...30 ...
Страница 31: ...31 ...
Страница 32: ...32 ...
Страница 33: ...33 ...
Страница 119: ...119 ...
Страница 120: ...120 ...