CONTROL OPTIONS AND SETTINGS
W
ATER
H
EATER
O
PTIONS
0-10V DC remote flow temperature set point
The hot water temperature is controlled by connecting an external 0-10V DC signal to the water heater (connections 15-16).
P5BB Analogue input Config (0=off 1=temp) (display D1).
This parameter must be set at "1" so the supplied 0-10 V dc signal will control the temperature set point.
Possible settings are:
0 =
0-10V control off
1 =
0-10V temperature set point control active
See also the following graph for the relation between the temperature and the control signal.
Values for illustration purposes, programmed parameter values can deviate!
0-10 Vdc control signal
tem
pe
ratu
re se
tting
°C
P2GB off
P2GA on
P2GC max.
P6CA max. Temperature set point
e.g. 90°C
P5CH min. temperature set point
e.g. 20°C (default)
P2GD offset Legionella
P5CI hysteresis Legionella
P5CD Legionella temperature