92
EF180
pre adjustment settings gas valve for BIC water heaters
Water heater
Type
Number of turns open (counter clockwise)
Nat. Gas G20 / G25
Propane G31
Butane G30
EF 80
1.5
0.75
0.5
EF100
3.5
1.5
1.25
EF120
2.25 *
1 *
0.75 *
EF150
2.25 *
1 *
0.75 *
EF180
4.25 *
2.25 *
2 *
* Both gas valves must be opened this number of turns.
21.2.4
Table 2
Pressure adjustment settings LEFT valve
Water heater
Type
“p-out” pressure at gas valve
Nat. Gas G20 / G25
Propane G31
Butane G30
EF120
-2 to 0 Pa
-4 to -2 Pa
-5 to -3 Pa
EF150
-2 to 0 Pa
-7 to -5 Pa
-8 to -6 Pa
EF180
-2 to 0 Pa
-7 to -5 Pa
-8 to -6 Pa
21.2.5
Table 3
Maximum fan speed has to be reduced to convert the boiler into a propane or B/P appliance.
Setting of parameter P4BD.
A sticker has to be pasted after converting the boiler into a propane or B/P appliance.
Mark the used gas and the parameter setting on this sticker.
PROPANE
PROPAN
PROPANO
PROPAAN
BUTANE/PROPANE
BUTAN/PROPAN
BUTANO/PROPANO
BUTAAN/PROPAAN
P4BD = 1
P4BD = 2
G31 P
G30/G31 B/P
adjust
adjust
adjust
adjust
max load
min load
4,8 %
5,1 %
7,0 %
7,3 %
O
2
10,8 %
10,6 %
9,3 %
9,1 %
CO
2
O.K.
O.K.
Содержание EcoForce EF100
Страница 2: ...2 ...
Страница 11: ...11 3 1 4 Cascade frames Frames are available to mount up to 4 EcoForce water heaters if required ...
Страница 24: ...24 ...
Страница 25: ...25 ...
Страница 26: ...26 ...
Страница 30: ...30 ...
Страница 31: ...31 ...
Страница 32: ...32 ...
Страница 33: ...33 ...
Страница 119: ...119 ...
Страница 120: ...120 ...