Cycle Data View (SE8)
Cycle Data View displays the cycle data of the operating outdoor
unit. Cycle Data View can display 26 different cycle datapoints on
the SSD.
For use on both heat pump and heat recovery systems.
Turn No. 5 on the master outdoor unit PCB
DIP switch bank SW01 to ON.
6HOHFWWKH³6YF´PRGHE\XVLQJWKH6:&IRUZDUGŹEXWWRQDQGWKH
6:&EDFNZDUGŻEXWWRQDQGWKHQSUHVVWKH6:&FRQILUP
ƔEXWWRQ
6HOHFWWKH³6(´IXQFWLRQE\XVLQJWKH6:&IRUZDUGŹEXWWRQDQG
WKH6:&EDFNZDUGŻEXWWRQDQGWKHQSUHVVWKH6:&
FRQILUPƔEXWWRQ
Select from “oP1” through “oP26” by using the SW03C forward
ŹEXWWRQDQGWKH6:&EDFNZDUGŻEXWWRQDQGWKHQSUHVV
WKH6:&FRQILUPƔEXWWRQ
Figure 34: Setting the Cycle Data View Function.
The Cycle Data View function begins. See table below for “oP1”
through ‘oP26” option information.
Option
Description
Display
Example
seg_1
seg_2
seg_3
seg_4
op1
Current High Pressure
P1
4,320.9 kPA (626.7 psi)
4
3
2
1
op2
Current Low Pressure
P2
1,234.2 kPA (179 psi)
1
2
3
4
op3
Inv 1 Pulse
h1
120 Hz
1
2
0
op4
Inv 2 Pulse
h2
30
3
0
op5
Fan RPMs
h3
110
1
1
0
op6
Degree of Subcooling
T1
5.3°C (41.5°F)
5
3
op7
Degree of Superheating
T2
-4.5°C (23.9°F)
-
4
5
op8
Outdoor Unit Temperature
T3
10°C (50°F)
1
0
0
op9
Suction Temperature
T4
43.4°C (110.1°F)
4
3
4
op10
Compressor 1 Discharge Temperature
T5
150°C (302°F)
1
5
0
op11
Compressor 2 Discharge Temperature
T6
124°C (255.2°F)
1
2
4
op12
Liquid Pipe Temperature
T7
10°C (50°F)
1
0
0
op13
Sc_in
T8
10°C (50°F)
1
0
0
op14
Sc_out
T9
10°C (50°F)
1
0
0
op15
Hex_total
T10
10°C (50°F)
1
0
0
op16
Hex_hi
T11
10°C (50°F)
1
0
0
op17
Hex_low
T12
10°C (50°F)
1
0
0
op18
Inlet Pipe Temperature of Indoor Unit
T13
-10°C (14°F
-
1
0
0
op19
Main 1 EEV
PLS1
1,940
1
9
4
0
op20
Main 2 EEV
PLS2
32
3
2
op21
SC EEV
PLS3
16
1
6
op22
Oil EEV
PLS4
50
5
0
op23
vi eev 1
PLS5
1,350
1
3
5
0
op24
vi eev 2
PLS6
8
8
op25
Operation Capacity of Indoor Units
IDU1
24,000
2
4
op26
Total Number of Indoor Units
IDU2
10
1
0
Table 44: Cycle Data View Datapoint Options.
OTHER CONTROLS
Setting Optional Modes