![LG Multi V 5 Скачать руководство пользователя страница 161](http://html.mh-extra.com/html/lg/multi-v-5/multi-v-5_service-manual_1892770161.webp)
161
Error Codes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No.
Description
Details
Causes
42
Master: 421
Slave 1: 422
Slave 2: 423
Outdoor unit low
pressure sensor
error.
Disconnection or short circuit of outdoor unit
low pressure sensor.
1. Check the connection on the outdoor unit
PCB.
2. Thermistor shorted or opened.
3. Check for 12 V DC between 12 V and GND
(red to black) for 5 V DC.
4. Check the Signal to GND (white to black) and
use correct chart from Troubleshooting section
to compare with actual system pressure.
43
Master: 431
Slave 1: 432
Slave 2: 433
Outdoor unit high
pressure sensor
error.
Disconnection or short circuit of outdoor unit
high pressure sensor.
Pressure sensor connectors.
High pressure sensor.
Low pressure sensor.
Images here are representative
of system components. Actual
component appearance depends
on model and system type.
Error Nos. 42 and 43
Is the sensor connected
to the PCB correctly?
End
Connect the sensor to the PCB correctly.
No
Yes
After the outdoor unit main
PCB is replaced, does the sys-
tem operate normally?
Yes
No
Replace corresponding pressure sensor.
Is the sensor operating
properly?
Test for V DC measurements and signal to GND.
If sensor measurements fall outside correct
measurements, replace sensor.
No
Yes