Error Codes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 24
Error No.
Description
Details
Causes
24
Master: 241
Slave 1: 242
Slave 2: 243
System has been
turned off by the
outdoor unit high
pressure switch.
Outdoor unit high pressure switch
error. Excessive increase in
outdoor unit compressor discharge
pressure.
1. Outdoor unit high pressure switch is defective.
2. Indoor unit fan or outdoor unit fan is / are defective.
3. Compressor check valve is clogged.
4. Pipe has been damaged.
5. Overcharge of refrigerant.
6. Defective EEV at the indoor or outdoor unit.
7. Outdoor unit is blocked during cooling mode; indoor unit
filter is clogged during heating mode.
8. Service valve is clogged.
9. Outdoor unit PCB is defective.
10. Check connection on the outdoor unit PCB.
11. Active path valve is defective.
12. Use chart in Troubleshooting section of the manual to
check signal output (V DC) versus actual pressure.
Is the high pressure
switch connected to
the PCB?*
No
Securely connect.
Has the high pressure
switch shorted out when the
system wasn’t operating?**
Yes
No
Does the error reappear
after the system is reset?
Yes
No
Is the service valve open?
Yes
Recheck--was the problem
temporary?
Replace connection cable.
Open the service valve.
No
Yes
Has the high pressure
switch terminal shorted
out?**
No
Replace high pressure switch.
Yes
Is the high pressure
>2500 kPa (measured at
the manifold gauge)?
No
Replace PCB.
Error CH24: Inverter Compressor
PCB.
Error CH109~154: Sub-unit PCB.
Yes
Does the high pressure
measured at the manifold
gauge match LGMV data?
No
Replace the high pressure sensor.
Yes
Check if piping is blocked
and fix as necessary.
*High pressure switch
**Check if the high pressure switch
connection on Main PCB.
connection has shorted out.
Images here are representative of system
components. Actual component appearance
depends on model and system type.