Pump Out for Heat Recovery Systems
Example of Pump Out Function When Slave2 Outdoor Unit Experiences Inverter Compressor Failure.
Liquid
Pipe
Closed
Open
High
Pressure
Vapor Pipe
Low
Pressure
Vapor Pipe
Liquid
Pipe
High
Pressure
Vapor Pipe
Low
Pressure
Vapor Pipe
Liquid
Pipe
High
Pressure
Vapor Pipe
Low
Pressure
Vapor Pipe
Liquid Pipe
Vapor Pipe
Service Ports
Refrigerant Charging Valve
Master Outdoor Unit
Heating Mode
Slave 2 Outdoor Unit
Heating Mode
Slave 1 Outdoor Unit
Heating Mode
1. Verify the liquid pipe and low pressure vapor pipe of the outdoor
unit are closed for Pump Out operation. Open the high pressure
vapor pipe service valve.
2. Operate Pump Out function.
3. Close high pressure vapor pipe of unit after Pump Out is
complete.
4. Replace inverter compressor, eliminate remaining refrigerant of
the corresponding outdoor unit, and perform Vacuum procedure
using Vacuum Mode.
5. Add refrigerant using the Refrigerant Auto Charge Function.
Figure 28: Close Up of Heat Recovery Service Ports and Refrigerant
Charge Valve.