![LG Multi V 5 Скачать руководство пользователя страница 211](http://html.mh-extra.com/html/lg/multi-v-5/multi-v-5_service-manual_1892770211.webp)
211
Error Codes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CHECKING MAIN PCB DC VOLTAGE
IN CASE OF POWER ON
Figure 81: Checking Main PCB DC Voltage (SMPS Voltage).
Checking Main PCB DC Voltage
Red
Black
Figure 82: Multi-Meter (Note the
Probe Color).
Vdc
5.0V
Vdc
12.0V
Vdc
12.0V
Vdc
5.0V
Main
Ext.
Comm
1
2
3
4
5
6
GND1 5V
Main
Ext.
2
1
4
3
6
5
8
7
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
23
24
25
26
27
28
GND2
5V
Table 91: Main PCB DC Voltage (SMPS Voltage) Measurements.
Check
Mode
Multi-Meter
Measured Value
Black
Red
Normal
Abnormal
Main Ext.
5V
DC
GND2
5V
4.5V~5.5V
9Ļ
12V
12V 11.5V~12.5V
9Ļ
Comm.
5V
GND3
5V
4.5V~5.5V
9Ļ
12V
12V 11.5V~12.5V
9Ļ
Use caution when measuring the voltage; GND is separated. There is risk of electric shock, and physical injury or death.
WARNING
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING