ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error Nos. 32 and 33
Error No.
Description
Details
Causes
32
Master: 321
Slave 1: 322
Slave 2: 323
Excessive in-
crease in outdoor
unit inverter
compressor1
gas discharge
temperature.
System / compressor shut off because of a
high discharge temperature at the outdoor unit
inverter compressor1.
1. System shutdown happens when discharge
pipe temperature rises >115°C (239°F)
for 10 seconds, or compressor dome
temperature equals 105°C (221°F) for 10
seconds.
2. Defective inverter compressor discharge
piping temperature sensor.
3. Refrigerant is leaking or there is under-
charge.
4. Defective EEV.
5. Defective liquid spray valve.
33
Master: 331
Slave 1: 332
Slave 2: 333
Excessive in-
crease in outdoor
unit inverter
compressor2
gas discharge
temperature.
System / compressor shut off because of a
high discharge temperature at the outdoor unit
inverter compressor2.
No
Yes
Is the discharge temperature
sensor resistance correct*
Replace the discharge
temperature sensor.
Is the amount of
refrigerant approrpriate
for the system?
Fix the leak and / or damaged
piping and recharge the
refrigerant.
Is there a refrigerant leak
or damaged piping?
Add or subtract the amount
of refrigerant.
Is the outdoor unit EEV
functioning normally while
system is in heating mode?
See the Troubleshooting
Main Compoenents section.
Replace the outdoor unit
EEV.
Is the piping
(strainer, etc.) clogged?
Check other system components
and operation conditions.
Fix if errors are found.
Replace strainer, etc.
No
Yes
No
Yes
No
Yes
No
Yes
* Resistance value of discharge temperature sensor
50°
) Nȍ
°F
Nȍ
°
) Nȍ
°
) Nȍ