44
MUL
TI V 5 Outdoor Unit Service Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
BASIC CONTROL
Main EEV Control
Main EEV operates with fuzzy logic to keep the degree of superheat (about 37.4°F) at the evaporator outlet stable during heating mode.
Degree of Superheat = Tsuction - Tevaporation
where,
• Tsuction = Temperature measured at the suction pipe sensor (°F).
• Tevaporation = Evaporation temperature equivalent to low pressure (°F).
Master and Slave Outdoor Unit EEV Control
Subcooling EEV Control
Subcooling EEV operates with fuzzy logic to keep the degree of subcool (about 59°F) at the outlet of the subcooler stable during cooling
mode.
Degree of Subcool = Tcondensation - Tliquid
where,
• Tliquid = Temperature at the outlet of the subcooler (°F).
• Tcondensation = Condensation temperature equivalent to high pressure (°F).
Master and Slave Unit EEVs / Fan Motor Control
Avoiding Excessively High Discharge Temperatures
After the main EEV opens to a predetermined amount (R410A: 800 pulses), and the discharge temperature is above 185°F in heating mode,
subcooling EEV control will operate to maintain compressor superheat.
Vapor Injection Flow Rate Control During Heating Mode
The degree of Superheat (VI_SH) = Subcooler out (°F) – Subcooler in (°F)
where
•
7G)9,B6+ )
•
)7G)9,B6+ î7G)
• 194°F > Td : VI_SH = 33.8°F
Fan Motor Control
Fan motor operates using Fuzzy logic.