Setting the Optional Modes
To access and set the different modes, first turn No. 5 on the master
outdoor unit PCB DIP switch bank SW01 to ON. Then, select the
³)XQF´³,GX´RU³6Y&´PRGHE\XVLQJWKH6:&IRUZDUGŹEXWWRQ
DQGWKH6:&EDFNZDUGŻEXWWRQDQGWKHQSUHVVWKH6:&
FRQILUPƔEXWWRQ
DIP-SW01
SSD
SW01C
(Confirm / Automatic
Address Setting Button)
SW01D
(Reset Button)
SW02C
(
Ż
Backward
Button)
SW03C
(
Ź
Forward
Button)
SW04D
(x Cancel
Button)
1 2
7
6
5
4
3
1 2
7
6
5
4
3
ON
OFF
• To set the optional modes / functions, all indoor units must be OFF.
Mode / function settings won’t save, nor will operate unless all indoor
units are OFF.
• If system power was reset, some modes / function settings will be automatically
saved in the EEPROM. Other modes / functions will reset when power is cycled
off. See next pages for details on specific modes / functions.
Mode Selection
Selection
Selection
Notes
Content
Display
Mode / Function Name
Display
Default
Options
Fault Detection
and Diagnostics
Fdd
Refrigerant Auto Charge (Cooling)
Fd1
-
Refrigerant Auto Charge (Heating)
Fd2
-
Refrigerant Auto Judge (Cooling)
Fd3
-
Refrigerant Auto Judge (Heating)
Fd4
-
Integrated Test Run
Fd7
-
-
All Indoor Unit Cooling Operation
Fd8, cooL
oFF
oFF, on
All Indoor Unit Heating Operation
Fd9, hEAt
oFF
oFF, on
Function
Func
Cool / Heat Selector Switch (Installed)
Fn1
oFF
oFF, oP1~oP2
Saved in EEPROM;
Off = Not Installed
Static Pressure Compensation
Fn2
oFF
oFF, oP1~oP3
Saved in EEPROM;
Used for ducted discharge.
Night Low Sound
Fn3
oP10
oP1~oP12
Saved in EEPROM.
Overall Defrost
Fn4
oFF
on, oFF
Saved in EEPROM.
Off = Split Coil / Frame
Allowed
Outdoor Unit Addressing
Fn5
0
0~254
Saved in EEPROM.
Snow Removal Assist / Rapid Defrost
Fn6
oFF
oFF, oP1~oP3
Saved in EEPROM.
Adjusting Indoor Unit Capacity
Fn7
oFF
oFF, oP1~oP2
Saved in EEPROM.
Adjusting Target Pressure
Fn8
oFF
oFF, oP1~oP6
Saved in EEPROM.
Low Ambient Kit
Fn9
oFF
on, oFF
Saved in EEPROM.
High Efficiency Mode (Cooling Operation)
Fn10
oFF
on, oFF
Saved in EEPROM.
High Efficiency Mode Cooling Operation
(Auto Dust Throw)
Fn11
oFF
oFF, oP1~oP5
Saved in EEPROM.
Smart Load Control
Fn14
oFF
oFF, oP1~oP3
Saved in EEPROM;
Can use in all applications
except DOAS. Energy
saving feature.
Figure 6: Location of DIP Switches and Setting Buttons on the Outdoor
Unit PCB.
Figure 7: No. 5 on DIP Switch Bank SW01 ON.
Table 19: Optional Modes.
OTHER CONTROLS
Setting Optional Modes