TI V 5 Outdoor Unit Service Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 10
Error No.
Description
Details
Causes
10
Indoor unit BLDC
fan motor commu-
nications error.
Indoor BLDC fan motor feedback signal has
been absent for at least 50 seconds.
1. Fan motor connector has been disconnect-
ed, removed, or malfunctioned.
2. Indoor fan motor lock has failed.
3. Indoor PCB error.
Is the connection
installed properly?
Yes
No
Connect properly.
Is fan motor
operating normally?*
Replace indoor unit fan motor.
*The indoor unit fan motor hall sensor is operating normally when the values measured are as shown below.
Yes
No
k
Replace indoor unit PCB**
Checking the Fan Motor Connections
1
4
5 6
7
1
5
6
7
4
4
4
4
Measure Each Terminal with the Tester
Tester
Hundreds k
ȍ +XQGUHGVNȍ
Hundreds k
ȍ +XQGUHGVNȍ
+
-
Normal Resistance (±10%)
** Replace the indoor unit PCB, perform the Auto Addressing procedure, and then input the
central control address.
WARNING
Check the fan motor connection to the PCB only when power is OFF. Electrical shock can cause physical injury or death.
Images here are representative of system components. Actual compo-