![LG Multi V 5 Скачать руководство пользователя страница 194](http://html.mh-extra.com/html/lg/multi-v-5/multi-v-5_service-manual_1892770194.webp)
194
MUL
TI V 5 Outdoor Unit Service Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 151, continued.
Location of the four-way valve connector on
the Main PCB (marked as “4way, CN09”).
Confirm the four-way valve coil is completely inserted.
Measure the four-way valve resistance.
Check the output voltage of the terminal socket
during heating operation (output should be 230 V AC).